Dimension: 17.7 mm Width x 105 mm Height
Trip-free design-breaker can not be defeated by holding the handle in the ON position
Captive screws cannot be lost
SWD (switching duty)- suitable for switching fluorescent lighting loads (in <= 20 Amp)
Field installable shunt trip and auxiliary switch subsequent mounting
Contact Position Indicator (red/green)
Possibility for sealing the toggle in ON or OFF position
Quick fastening with two lock-in positions on IEC/EN 60715
Detailed Description: Eaton / Cutler Hammer FAZ series type C 1-Pole DIN rail circuit breaker is ideal for branch service applications where medium levels of inrush current are expected. It provides two levels of short-circuit protection for optimum performance. Circuit breaker is a current limiting device having an interrupting capacity of 10 kilo-Amps that reduces the let-through current and energy, which can damage the circuit. It has a current rating of 15 Amps and voltage rating of 125/250 VDC. It features instantaneous trip current of 5 - 10X that causes the circuit breaker to trip without intentional time delay. Circuit breaker is UL listed.
Dimensions | 17.7 mm Width x 105 mm Height |
Amperage Rating | 15 Amp |
Application | For Convenience Receptacle Circuits (Internal/External), Motor Control Circuits, Load Circuits Leaving the Equipment (External), Hacr Equipment (Heating, Air Conditioning, Refrigeration), (Internal/External), Plc I/O Points, Computers, Power Supplies, Control Instrumentation, Relays, UPS, Power Conditioners |
Brand | Eaton / Cutler Hammer |
Connection | Screw Terminal |
Environmental Conditions | >= 20,000 Operations Endurance |
Frame | 45 |
Interrupt Rating | 10 Kilo-Amp |
Item | Branch Circuit Breaker |
Mfr. # | FAZ-C15/1-NA-DC-SP |
Mounting | DIN-Rail |
Number Of Poles | 1 |
Standards | UL 489 Listed File #E235139, CSA Certified C22.2 No.5-02, VDE/ABS/RoHS Compliant |
Trip Range | 5 - 10 x In |
Trip Type | C-Curve, Thermal-Magnetic |
Type | EMD |
Voltage Rating | 125/250 Volt |
Wire Size | (1) 18-6 AWG, (2) 18-10 AWG |