Uniquely designed with two dials
Dial 1 to allow FLA adjustment across the range of the frame size
Dial 2 selects the type of motor protection - auto 1 for standard efficiency, auto 2 for high energy efficient motors, dial 2 also allows for traditional manual motor protection from 6 to 13 times the selected FLA
+/- 5% Typical accuracy range
Extensive selection of snap-in field installable accessories and terminals same as the equivalent thermal magnetic circuit breaker
Detailed Description: Schneider Electric / Square D I-Line® Powerpact® Molded Case 3-Pole Motor circuit protector has current rating of 100 Amps, voltage rating of 600 Volts and AIC rating of 100 kilo-Amps at 480 Volts. It is suitable for reverse fed applications that has features line/load side lug terminals, MCP and current limiting. 3-Phase breaker has magnetic protection with feed-thru type connection and is UL listed.
Application | Distribution |
Brand | PowerPact H |
Catalog Description | Square D,MOTOR CIRCUIT PROTECTOR 600V 150A,150 A,150 A,348...1690 A,58...130 A,3P,50 kA 600 V AC-125 kA 240 V AC-100 kA 480 V AC,600 V AC,600 V AC,L,Motor Circuit Protector,PowerPact,UL, CSA, IEC,electronic,unit mount |
Connection | Lugs, line;lugs, load; AWG 14...AWG 3/0 aluminium/copper terminal |
GTIN |
00785901835677 |
Height | 0.000 |
Height Unit | IN |
Item Status | A |
Length | 3.39 |
Length UOM | IN |
Mfr. # | HLL36150M74 |
Number Of Poles | 3 |
Special Features | Modbus;Ethernet |
Trip Type | Thermal-magnetic |
Type | Motor Circuit Protector |
UNSPSC | 39121616 |
Width | 4.09 |
Width UOM | IN |