Dimension: 5 Inch Width x 6.740 Inch Depth x 11.860 Inch Height
Their primary functions are to provide a means to manually open a circuit and automatically open a circuit under overload or short circuit conditions
Thermal-magnetic circuit breakers use bimetals and electromagnetic assemblies to provide overcurrent protection
Their characteristic inverse time tripping under overload conditions is ideally suited for many applications varying from residential to heavy industrial loads
Detailed Description: Schneider Electric/Square D I-Line® LA 2-Pole Molded case circuit breaker has 400 Amps frame. It has a current rating of 350 Amps, voltage rating of 600 VAC, 250 VDC and measures 5 Inch x 6.740 Inch x 11.860 Inch. AB-Phase breaker has an interrupt rating of 22 kilo-Amps at 600 VAC, 10 kilo-Amps at 250 VDC. It has I-line style plug-in type connection. Circuit breaker is UL listed and CSA/IEC/NOM certified.
Brand | I-LINE |
Catalog Description | Square D,MOLDED CASE CIRCUIT BREAKER 600V 350A,25 kA at 600 V AC-42 kA at 240 V AC-30 kA at 480 V AC,250 V DC-600 V AC,250 V DC-600 V AC,2P,350 A,350 A,LA,UL Listed,circuit breaker,thermal-magnetic |
GTIN |
00785901358435 |
Height | 11.0 |
Height Unit | IN |
Item Status | A |
Length | 5.84 |
Length UOM | IN |
Mfr. # | LA26350AB |
UNSPSC | 39121616 |
Width | 6.0 |
Width UOM | IN |